892M / 894M

Key Features:

• Universal DC analog I/O ranges provide flexi-bility for changing application requirements.
• Individual channel input/output scaling displays signal values in engineering units.
• Track and hold function enables easy identification of critical events and their corresponding signal values.
• 200-character equation fields (50-char. max. on 895/896M) support complex transfer functions.
• Software simulation feature allows off-line testing of equations to quickly check output signal response for a variety of conditions.
• Diagnostic LEDs provide quick, visual indication of an out-of-range input value.
• Pulse-width modulation capability allows the user to vary the output signal’s pulse width on a user-defined carrier frequency.
• Solid-state relays provide on/off control or local alarms with failsafe/ nonfailsafe capability.
• Windows XP/Vista®/7
• Operating temperature range: -25 to 70°C (-13 to 158°F).

Product Details

Input Ranges
DC Current: 0 to 22mA
DC Voltage: ±100V DC
AC Current: 0 to 20A AC (with external sensor)
Output Ranges
0 to 1mA, 0 to 20mA, 4 to 20mA DC
0 to 5V, 0 to 10V DC
Limit Alarm
SPDT electro-mechanical relay (-1500 unit only)

Environmental


Ambient Temperature
Operating: -25 to 70°C (-13 to 158°F).
Storage: -40 to 85°C (-40 to 185°F).
Relative Humidity
5 to 95%.
Power Requirements
10 to 36V DC. 110mA @ 24V. 170mA @ 15V.
Isolation (optical)
4-way (input/output/relay/power).
1500V AC for 60 seconds or 250V AC continuous.
Radiated Field Immunity (RFI)
EN61000-4-3, EN50082-1.
Electromagnetic Field Immunity (EMI)
Less than ±0.25% of output span effect under the influence of electromagnetic fields from switching solenoids, commutator motors, and drill motors.
Electrical Fast Transient (EFT)
EN61000-4-4, EN50082-1.
Surge Withstanding Capability (SWC)
EN61000-4-5, EN50082-1.
Electrostatic Discharge (ESD)
EN61000-4-2, EN50082-1.
Radiated Emissions
EN50081-1 for Class B equipment.
Approvals
CE, UL listed (USA, Canada).
UL3121 – general product safety.

Configuration


Software Configuration
Units are fully programmable via the Windows XP/Vista/7IntelliPack Configuration
Program. Configuration downloads from PC through EIA232 serial port using Acromag 800C-SIP kit.
Field Configuration
Output, zero/full-scale, relay set point and dead band are configurable via push-buttons and a standard calibrator.
LED Indicators
LEDs indicate power, status, calibration, and alarm.