Input Ranges – Ranges are selectable for a 3-channel group. Thermocouple (user-selectable type) – Type J, K, T, R, S, E, B, or N. DC Millivolts (user-selectable range) – ±100mV or ±1V DC. Network Communication – EtherNet/IP or Modbus TCP/IP 10/100Mbps with automatic data rate negotiation. Power Requirement – 15 to 36V DC supply (2 Watts) required. Approvals – CE/ATEX marked. – UL, cUL listed, Class I; Div. 2; Groups A, B, C, D. – EtherNet/IP, Modbus/TCP conformance tested. Noise Rejection – Normal Mode: Better than 40dB @ 60Hz. – Common Mode: Better than 140dB @ 60Hz. Input Filter Bandwidth – -3dB at 3Hz, typical. Input Conversion Rate – 80mS per channel. Ambient Temperature and Humidity – Operating: -25 to 70°C (-13 to 158°F). – Relative humidity: 5 to 95%, non-condensing. Isolation – 1500V AC for 60 seconds or 250V AC continuous. – 3-way isolation between I/O, network, and power. |