Anybus X-Gateway CANopen

Key Features:

Anybus X-gateway CANopen

 

family allows any CANopen enabled device with slave functionality to communicate with almost any other fieldbus or Industrial Ethernet network as it provide CANopen Master (Manager) or Slave functionality on the CANopen network and Slave/Adapter functionality to all popular fieldbusses such as Profibus, DeviceNet, Modbus, ControlNet and for industrial Ethernet with Profinet, EtherNet/IP, EtherCAT and Modbus TCP

 

• Connects CANopen slave devices to 10 Fieldbus and Industrial Ethernet networks
• Provides CANopen Master/Slave functionality on one side, and Slave functionality with the other network
• Allows for transparent transfer of I/O data between CANopen and another network
• CANopen Master (Manager) functionality allows for connection of up to 126 CANopen slave devices
• High performance with short throughput delay, max 5 ms
• Dual Port switched Ethernet allows daisy chaining on all Ethernet interfaces
• Compatible with all leading PLCs from manufacturers such as, Siemens, Allen Bradley, Schneider etc..
• Included Anybus Configuration Manager CANopen for easy configuration. No programming required
• Fieldbus or Ethernet slave interface is configured with a standard device description file (GSD / EDS)
• Global free technical support and consultancy
• 3 year product guarantee from date of shipment

Product Details

Anybus X-gateway CANopen 


Max amount of slaves: 126

CANopen network connector:  DSUB9M

Baud rate:  Up to 1 Mbit/s

I/O data:  128 PDOs Receive/128 PDOsTransmit, 510 bytes IN/OUT

Extras: CANopen specification DS301 v4.0.2

Certifications


UL File number: E203225

Hazardous Locations ATEX :
CLASS 1, DIVISION 2, GROUPS A, B, C AND D, T4
Zone 2, Cat 2
(except Modbus RTU)

Electrical Characteristics 


Power: 24 VDC +/- 10 %

Current consumption: Typical 150 mA 

Hardware Characteristics 


Reverse voltage protection: Yes

Short circuit protection: Yes

Galvanic isolation on subnetwork: Yes

Environmental Characteristics 


Operating temp: -25 to 55 C,

Storage temp:  -40 to 85 C,

Relative Humidity:  5-95 % non-condensing

Installation altitude:  Up to 2 000 m 

Immunity and Emission for Industrial Environment


Electrostatic discharge  +/- 4 kV  EN 61000-4-2
Electromagnetic RF fields  10 V/m 80 MHz – 1 GHz
3 V/m 1,4 GHz – 2,0 GHz
1 V/m 2,0 GHz – 2,7 GHz
EN 61000-4-3 
Fast Transients  +/- 1 kV  EN 61000-4-4
Surge protection  +/- 1 kV  EN 61000-4-5
RF conducted interference  10 V/rms  EN 61000-4-6
Emission (at 10 m)  40 dB 30 MHz – 230 MHz
47 dB 30 MHz – 1 GHz
EN 55016-2-3 