XT120

Key Features:

Designed to offer an isolated Ethernet network interface for up to eight differential current input
Channels. The Isolated differential inputs deliver better measurements, superior noise rejection, and
Eliminates the need for current loop isolators.

• Easy setup with Windows software via USB.
• Low input impendance (27 ohms) reduces loading on current loops.
• User-configurable sample averaging (1-200) on a per-channel basis.
• 10ms network updates for all 8 input channels.
• i2o peer-to-peer updates based on change-of-state and/or timed updates.
• High-resolution 16-bit Σ∆ A/D converter ensures precise, high accuracy measurements.
• High-Density 22.5mm wide package with pluggable, front-facing terminals.
• Dual Ethernet 10/100 ports (auto-negotiation) reduce switch port requirements.
• 1500V AC isolation (between I/O, power, and network ports) and surge/transient protection.
• Supports bussed/rail and redundant power.
• -40°C to +70°C wide temperature operation.
• Withstands 25g shock and 4g vibration.
• CE compliant. UL/cUL Class 1 Div 2 Zone 2 approvals.

Product Details

Performance Specifications

USB Interface


USB Connector
Type: USB Mini-B type socket, 5-pin.
Data rate: 12Mbps. USB v1.1 and 2.0 compatible.
Maximum cable length: 5.0 meters.
USB Transient Protection
Transient voltage suppression on power and data lines.
Driver
Not required. Uses Windows HID drivers.

Input


Output Channel Configuration
– 16 DC voltage outputs.
Output Ranges (per-channel basis)
– ±5V, ±10V DC (at ±1mA). User-configured on a per-channel basis.
Output Impedance
– 1 ohm maximum.
Output Resolution and Accuracy
– Resolution (±10V): 16-bit maximum, 0.00166%.
– Resolution (±5V): 15-bit maximum, 0.00305%.
– Accuracy: Better than 0.05% of range.

Ethernet Communication


Configuration
– Failsafe or non-failsafe (user-configurable) relay trips on power or link-loss failure.
Type
– SPST-NO, 1 Form A, Class I, Division II approved.
Rating
– 3A @ 24V DC/250V AC, 100,000 cycles general.
– 2A @ 24V DC/250V AC, Hazardous locations.
Maximum Switching Voltage and Power
– 250V AC / 750VA, 125V DC / 90W.

Environmental


Internal Switch or Hub/Repeater
– Dual-port Ethernet switch.
– User-configurable as a true switch (default mode) or low-latency hub.
Network Connector [10/100 Base-T(X)Copper]
– One or two 8-pin RJ-45 connectors.
– Automatic MDI/ MDI-X. 100m communication distance.
Network Connector (100 Base-FX Fiber-optic)
– One multi-mode with SC connector. 2km communication distance. Full/half-duplex, selectable.
Protocols
– Modbus TCP/IP, UDP/IP, i2o peer-to-peer.
Addressing
– StaticIP, DHCP, BootP.
Ethernet Modbus TCP/IP Sockets/Sessions
– 1-10 socket/sessions user-configurable.
Ethernet Redundancy
– Compatible with STP, RSTP, or any ring scheme.

Environmental


Operating and Storage Temperature
– Operating: -40 to 70°C (-40 to 158°F).
– Storage: -40 to 85°C (-40 to 185°F).
Power Requirements
– 18-36V DC. Redundant, diode-coupled terminals.
– 4.8W (copper ports), 5.8W (fiber-optic ports).
Isolation
– I/O, power, relay and Ethernet port-to-port.
– Peak: 1500V AC, ANSI/ISA-82.01-1988.
– Continuous: 250V AC, 354V DC (150V AC ch-ch).

Safety Approvals


- CE marked and UL/cUL Listed.
– Hazardous Locations: Class I; Div 2; A, B, C, D.
– Open board units: UL Recognized.
– Shock and Vibration Immunity (in enclosure)
– Mechanical Shock: 50g (3ms), 30g (11ms).
– Random Vibration: 5g, (5-500Hz).