XCP5908/16 Series

Key Features:

8 or 16-Port IEC61850-3 Certified Industrial Rack-Mount Secure Modbus Gateway

 

• Remotely access Modbus RTU/ASCII devices, convert to Modbus TCP
• Supporting advanced Modbus Features. Configuration via Web Browser
• IEC61850-3 certified, can be easily set up into IEC61850-3 substations
• Industrial EMC protection, wide temperature operation, -40°C~85°C
• Redundant Power Input for fault protection, either 24~48 VDC or High- Voltage AC/DC (100~240VAC or 100~370VDC)
• 6 Fast-Ethernet interfaces, either RJ45 or SFP slot
• 8 or 16 RS-232/RS-485/RS-422 Serial ports, with or without isolation
• Supporting VIrtualCOM and RSTP, security with IPsec or OpenVPN C/S
• Configuration via Web Browser/ Serial Console / Telnet/ Windows Utility

Product Details

Protocol Specification

 

Model Name XCP5908 (8 ports);
XCP5916 (16-ports)
Network interface
Speed IEEE 802.3 10BaseT
IEEE 802.3u 100BaseT(X) – RJ45 version
IEEE 802.3u 100Base-FX – SFP version
Connector ports RJ45 x 6 (RJ45 version)
SFP x 6 (SFP version)
Serial Interface
Connector D-Sub9 (DB models, supporting only 5-pin RS-232 mode) or
5.08mm 5-Pin Terminal block (TB Models)
Ports 8 (XSP5908) or 16 (XSP5916)
Mode RS-232/422/485 Software selectable
Serial port isolation 3 kV isolation (SiS version only)
Baud Rate 1,200 ~ 921,600 bps software selectable
Parity None, Odd, Even, Mark, Space
Data Bits 5, 6, 7, 8 software selectable
Stop Bits 1, 2 software selectable
Flow Control None, Xon/Xoff, RTS/CTS (RS-232 only)
Power
Input Voltage Redundant 24-48 VDC or

Redundant 100-240 VAC/ 100-370 VDC (HV Series)

Input Current 0.73 A @ 24 VDC

0.35 A @ 100 VAC

0.20 A @ 100 VDC

Power Consumption Approximately 20 W
Power Redundancy Yes
Connector 10-Pin Terminal Block
Reverse Polarity Protection Yes
Physical Characteristics
Housing
Dimension (W x H x D)
Weight
Installation
Reset Button
IP30 SPCC housing
440.6 x 44 x 309 mm (1U Rack-mount)
4 kg
19” Rack mount (Rack-mount kit included)
Yes
Environmental Limits
Operating Temperature
Storage Temperature
Ambient Relative Humidity
-40°C~85°C (-40°F~185°F)
-40°C~85°C (-40°F~185°F)
5%~95%, 55°C (Non-condensing)
Software
Protocols IPv4, ICMP, TCP, UDP, DHCP Client, SNMPv1,v2c,v3, HTTP, HTTPS, Telnet, RFC2217, 802.1D-2004 RSTP, Security through OpenVPN Client/Server or IPsec VPN (peer-to-peer or peer-to-side) with up to 37.9Mbps VPN throughput, PPTP, and SMTP/TLS
Configuration AGATEL Management Utility, Web UI, Telnet, Console
VirtualCOM Windows/Linux redirection software
Modbus Features
Supported Modes Ethernet: Modbus TCP Server/Client(or VCOM);
Serial: Modbus RTU/ASCII (master/slave)
Maximum number of clients/slaves Modbus TCP: Maximum 16 clients;
Maximum 247 slaves

 Regulatory Approvals  

 

Regulatory Approvals
Safety EN 61010-2-201
EMC FCC Part 15, Subpart B, Class B, EN 55032, Class B, EN 61000-6-2 Class B, EN 61000-3-2,

EN 61000-3-3, EN 55024, EN 61000-6-4, IEC 61850-3 / IEEE 1613

Test Item Value Level
IEC 61000-4-2 ESD Contact Discharge
Air Discharge
±8kV

±15kV

4

4

IEC 61000-4-3 RS Radiated (enclosure) 10 V/m 3
IEC 61000-4-4  

EFT

AC Power Port
DC Power Port
Signal Port
±4.0KV

±4.0KV

±4.0KV

4

4

4

IEC 61000-4-5 Surge AC Power Port
AC Power Port
DC Power Port
DC Power Port
Signal Port
Line-to Line±2.0KV
Line-to Earth±4.0KV
Line-to Line±1.0KV
Line-to Earth±2.0KV
Line-to Earth±2.0KV
4

4

3

3

4

IEC 61000-4-6  

CS

AC Power Port
DC Power Port
Signal Port
10 V rms 3
IEC 61000-4-8 PFMF Enclosure 100 A/m 5
IEC 61000-4-10 Damped Oscillato- ry Magnetic Field Enclosure 100 A/m 5
IEC 61000-4-11 DIP AC Power Port
IEC 61000-4-12 Damped
Oscillatory
AC Power Port
Signal Port
2.5 KV common, 1 KV differential

2.5 KV common, 1 KV differential

3

3

Shock MIL-STD-810F Method 516.5
Drop (Freefall) MIL-STD-810F Method 516.5
Vibration MIL-STD-810F Method 514.5 C1 & C2
RoHS Yes
MTBF XCP5916-6S-SI-HV: 9.18 years; XCP5916-6S-SI: 8.63 years
Warranty 5 Years