XGP5908/XGP5916 Series

Key Features:

  XGP5908/XGP5916 Series

Industrial Protocol Gateway

• Dual 10/100Mbps Ethernet ports, Embedded PPTP, IPsec or OpenVPN for enhanced security
• Remotely monitor, manage, and control industrial field devices
• Relay out indicator for Network link-status
• LCM display with 4-key touch pad for configuration
• Same hardware platform for different protocol conversion (Modbus TCP/RTU/ASCII, DNP3.0 TCP or serial, IEC 60870-5-101,
IEC 60870-5-103, IEC 60870-5-104, IEC 61850)
• User friendly configuration with a Java-Based Windows utility
• Integrated RSTP redundancy

Product Details

Protocol Specification

 

IEC61850 Server/ Client
Supported Functions •   Generic access to the data (Read, Write)

•   Clock Synchronization

•   8 Logical Devices per Port

•   GOOSE (Generic Object Oriented Substation Event) – a GOOSE message will be generated by the gateway automatically upon event(*)

(*)Being other protocols not Real-Time, there is no guarantee that GOOSE message is generated within
1 ms from the event itelf.

Supported Control Type of commands •   Direct-with-Normal-Security – Select Before Operate (SBO)-with-Normal-Security

•   Direct-with-Enhanced Security – Select Before Operate (SBO)-with-Enhanced-Security

Implemented Protocol Subsets •   IEC 61850-6 (Substation Configuration Language Description: SCL)

•   IEC 61850-7-1 (Principles and Models)

•   IEC 61850-7-2 (Abstract Communication Service

•   Interface: ACSI

•   IEC 61850-7-3 (Common Data Classes: CDC)

•   IEC 61850-7-4 (Logical Nodes and data Object Classes)

•   IEC 61850-8-1 (Mapping to Manufacturing Message Specification: MMS)

•   Edition 1 & Edition 2 are both Supported

DNP3 Server/ Client/ Master/ Slave
General Specifications •   Serial Mode or Ethernet with TCP or UDP Mode

•   Server side supports serving up to 5 client in TCP Mode

•   Client side in a single RS-485 port, supports connecting up to 16 IEDs

•   Client side supports connecting up to 16 IEDs

•   Maximum Fragment size 2048 octets

•   Protocol implementation with configurable parameters conforms to IEEE Std 1815-2012 level 2

Supported Functions •   Time Synchronization generic access to the data(Read, Write)

•   Commands with or without preselection (Select, Operate, Direct Operate)

•   Transmission of time-tagged events

•   Counter management (Immediate Freeze, Freeze and Clear)

•   Self-address

Supported DNP3 Object Library •   Binary Inputs up to 8000 pts

•   Binary Outputs up to 2000 pts

•   Double Inputs up to 4000 pts

•   Analog Inputs up to 250 pts

•   Analog Outputs up to 250 pts

•   Counters up to 250 pts

Modbus Server/ Client/ Master/ Slave
General Specifications •   Support Modbus RTU and ASCII in Serial mode

•   Support Modbus in TCP mode

•   For Modbus Client in TCP mode, support connecting up to 64 Modbus servers

•   For Modbus Server in TCP mode, support serving up to 64 Modbus clients

•   Support maximum number of data points in read direction: 8000 pts

•   Support maximum number of commands in write direction: 4000 pts

Supported Function Codes 1: Read Coils

2: Read Discrete Inputs

3: Read Holding Registers
4: Read Input Registers

5: Write Single Coil

6: Write Single Register
15: Write Multiple Coils

16: Write Multiple Registers

43/14: Read Device Identification (server side only)

Supported Exception Codes 1: illegal function
2: illegal data address
3: illegal data value
4: server device failure
6: server device busy
IEC 60870-5-101 Master/ Slave
General Specifications •   Protocol implementation with configurable parameters conforms to the IEC 60870-5-101 edition 2 specification

•   Process Information in Monitor and Control Direction

•   Balanced and Unbalanced Modes

•   CP24Time2a or CP56Time2a timestamp for monitor direction report

Supported Functions •   Station Initialization

•   Interrogation

•   Read Procedure

•   Cyclic Data and Spontaneous Transmission (Slave Side only)

•   Clock Synchronization

•   Transmission of Integrated Totals

•   Direct and SBO command

Supported Data Types •   Monitors Points:

Each supports up to 1000 pts: Single Point, Double Point, Step Position, Bit String, Measured with Normalized Value, Measured with Scaled Value, Measured Short Floating Point Value, Integrated Totals

•   Control Points:

Each supports up to 500 pts: Single Command, Double Command, Regulating Step Com mand, Set Point Command with Normalized Value, Set Point Command with Scaled Value, Set Point Command Short Floating Point, Bit string

IEC 60870-5-103 Master/ Slave
General Specifications •   Protocol implementation with configurable parameters conforms to the IEC 60870-5- 103:1997

•   Master supports connecting up to 16 IEDs

•   Process Information in Monitor and Control Direction

•   Unbalanced Modes

Supported Functions •   Station Initialization, Supports reset FCB and CU

•   General Interrogation

•   Clock Synchronization

•   Command Transmission

•   Test Mode

•   Blocking of Monitor Direction

Supported Information •   Monitor direction:

*  Status indications in monitor direction: from <16> to <30>

*  Supervision indications in monitor direction: <32>, <33>, from <35> to< 39>, <46>, <47>

*  Earth fault indications in monitor direction: from <48> to <52>

*  Fault indications in monitor direction: from <64> to <93>

*  Auto-reclosure indications in monitor direction: from <128> to <130>

*  Measurands in monitor direction: from <144> to <148>

•   Control direction:

General commands in control direction: from <16> to <19>, from <23> to <26>

IEC 60870-5-104 Server/ Client
General Specifications •   Server side supports serving up to 5 client

•   Client side supports connecting up to 10 IEDs

•   Protocol implementation with configurable parameters conforms to the IEC 60870-5-104 specification edition 2

•   Process Information in Monitor and Control Direction

•   CP56Time2a timestamp for Control Commands

Supported Functions •   Station Initialization

•   Interrogation

•   Read Procedure (Server side only)

•   Cyclic Data and Spontaneous Transmission (Server side only)

•   Clock Synchronization

•   Transmission of Integrated Totals

•   Direct and SBO command

Supported Data Types •   Monitors Points:

Each supports maximum 1000 pts: Single Point, Double Point, Step Position, Bit String, Mea sured with Normalized Value, Measured with Scaled Value, Measured Short Floating Points Value, Integrated Totals.

•   Control Points:

Each supports maximum 500 pts: Single Command, Double Command, Regulating Step Command, Set Point Command with Normalized Value, Set Point Command with Scaled Value, Set Point Command Short Floating Point, Bitstring.

•   Event Logging (Server Side only) Universal Event Buffer up to 20,000 Events

Technical Specifications

 

Network Interface
Ethernet Port 2 x RJ-45
LAN Mode Dual Subnets or RSTP LAN Redundancy
Compliance IEEE 802.3 10BASE-T

IEEE 802.3u 100BASE-T(X)

Serial Interface
Connector RJ-45
Port 8 or 16
Mode RS-232/422/485, software selectable
Baud Rate 1,200~921,600 bps
Parity None, Odd, Even
Data Bits 5,6,7,8
Stop Bits 1,2
Power Characteristics
Connector IEC 60320-1 C14 AC Power Inlet (AC models)
5.08mm 3-pin Lockable Terminal Block (DC models)
Input Voltage 24-48 VDC for DC models
100-240 VAC for AC models
Power Consumption 0.54A @ 24 VDC

0.21A @ 100 VAC

Power Redundancy No
Reverse Polarity Protection Yes (DC Input only)
Mechanicals
Housing IP30 protection, metal housing
Dimensions (W x H x D) 436 mm x 43.5 mm x 200 mm
Installation 19” Rack Mount
Reset Button Yes
Weight 3.2kg (16 ports) / 3.0 kg ( 8 ports)
Environmental Limits
Operating Temperature -20°C ~ 70°C (-4°F ~ 158°F)
Storage Temperature -40°C ~ 85°C (-40°F ~ 185°F)
Ambient Relative Humidity 5 ~ 95% RH, (non-condensing)
Software
Protocols IPv4, ARP, ICMP, TCP, UDP, DHCP Client, DNS Client, Telnet, HTTP, HTTPS, SMTP/TLS,

SNMP v1/v2c/v3, Syslog, RSTP, OpenVPN or IPsec VPN (peer-to-peer or peer-to-side), with a maximum VPN throughput of 37.9Mbps(*), and PPTP

* Testing conditions may affect the VPN throughput

 

 Regulatory Approvals  

 

Regulatory Approvals
Safety EN 60950-1
EMC FCC Part 15, Subpart B, Class A
EN 55032, Class AEN 61000-3-2EN 61000-3-3EN 55024
Test Item Value Level
IEC 61000-4-2 ESD Contact Discharge
Air Discharge
±8KV

±15KV

4

4

IEC 61000-4-3 RS Enclosure 10 V/m 3
IEC 61000-4-4 EFT AC Power Port
DC Power Port
Signal Port
±4.0KV

±4.0KV

±2.0KV

4

4

3

IEC 61000-4-5 Surge AC Power Port
AC Power Port
DC Power Port
DC Power Port
Signal Port
Line-to Line±2.0KV
Line-to Earth±4.0KV
Line-to Line±1.0KV
Line-to Earth±2.0KV
Line-to Line±2.0KV
4

4

3

3

4

IEC 61000-4-6 CS AC Power Port
DC Power Port
Signal Port
10 Vrms

10 Vrms

10 Vrms

3

3

3

IEC 61000-4-8 PFMF Enclosure 1A/m 3
IEC 61000-4-11 DIP AC Power Port
Shock IEC60068-2-27
Drop ISTA Test Procedure 2A
Vibration IEC60068-2-64
RoHS Yes
MTBF

(MIL-HDBK-217F)

XGP5908-SI-DC: 19.00 years; XGP5908-SI-US/EU: 19.03 years

XGP5916-SI-DC: 13.38 years; XGP5916-SI-US/EU: 13.38 years

Warranty 5 years