IEC61850 Server/ Client | |
Supported Functions | • Generic access to the data (Read, Write)
• Clock Synchronization • 8 Logical Devices per Port • GOOSE (Generic Object Oriented Substation Event) – a GOOSE message will be generated by the gateway automatically upon event(*) (*)Being other protocols not Real-Time, there is no guarantee that GOOSE message is generated within |
Supported Control Type of commands | • Direct-with-Normal-Security – Select Before Operate (SBO)-with-Normal-Security
• Direct-with-Enhanced Security – Select Before Operate (SBO)-with-Enhanced-Security |
Implemented Protocol Subsets | • IEC 61850-6 (Substation Configuration Language Description: SCL)
• IEC 61850-7-1 (Principles and Models) • IEC 61850-7-2 (Abstract Communication Service • Interface: ACSI • IEC 61850-7-3 (Common Data Classes: CDC) • IEC 61850-7-4 (Logical Nodes and data Object Classes) • IEC 61850-8-1 (Mapping to Manufacturing Message Specification: MMS) • Edition 1 & Edition 2 are both Supported |
DNP3 Server/ Client/ Master/ Slave | |
General Specifications | • Serial Mode or Ethernet with TCP or UDP Mode
• Server side supports serving up to 5 client in TCP Mode • Client side in a single RS-485 port, supports connecting up to 16 IEDs • Client side supports connecting up to 16 IEDs • Maximum Fragment size 2048 octets • Protocol implementation with configurable parameters conforms to IEEE Std 1815-2012 level 2 |
Supported Functions | • Time Synchronization generic access to the data(Read, Write)
• Commands with or without preselection (Select, Operate, Direct Operate) • Transmission of time-tagged events • Counter management (Immediate Freeze, Freeze and Clear) • Self-address |
Supported DNP3 Object Library | • Binary Inputs up to 8000 pts
• Binary Outputs up to 2000 pts • Double Inputs up to 4000 pts • Analog Inputs up to 250 pts • Analog Outputs up to 250 pts • Counters up to 250 pts |
Modbus Server/ Client/ Master/ Slave | |
General Specifications | • Support Modbus RTU and ASCII in Serial mode
• Support Modbus in TCP mode • For Modbus Client in TCP mode, support connecting up to 64 Modbus servers • For Modbus Server in TCP mode, support serving up to 64 Modbus clients • Support maximum number of data points in read direction: 8000 pts • Support maximum number of commands in write direction: 4000 pts |
Supported Function Codes | 1: Read Coils
2: Read Discrete Inputs 3: Read Holding Registers 5: Write Single Coil 6: Write Single Register 16: Write Multiple Registers 43/14: Read Device Identification (server side only) |
Supported Exception Codes | 1: illegal function 2: illegal data address 3: illegal data value 4: server device failure 6: server device busy |
IEC 60870-5-101 Master/ Slave | |
General Specifications | • Protocol implementation with configurable parameters conforms to the IEC 60870-5-101 edition 2 specification
• Process Information in Monitor and Control Direction • Balanced and Unbalanced Modes • CP24Time2a or CP56Time2a timestamp for monitor direction report |
Supported Functions | • Station Initialization
• Interrogation • Read Procedure • Cyclic Data and Spontaneous Transmission (Slave Side only) • Clock Synchronization • Transmission of Integrated Totals • Direct and SBO command |
Supported Data Types | • Monitors Points:
Each supports up to 1000 pts: Single Point, Double Point, Step Position, Bit String, Measured with Normalized Value, Measured with Scaled Value, Measured Short Floating Point Value, Integrated Totals • Control Points: Each supports up to 500 pts: Single Command, Double Command, Regulating Step Com mand, Set Point Command with Normalized Value, Set Point Command with Scaled Value, Set Point Command Short Floating Point, Bit string |
IEC 60870-5-103 Master/ Slave | |
General Specifications | • Protocol implementation with configurable parameters conforms to the IEC 60870-5- 103:1997
• Master supports connecting up to 16 IEDs • Process Information in Monitor and Control Direction • Unbalanced Modes |
Supported Functions | • Station Initialization, Supports reset FCB and CU
• General Interrogation • Clock Synchronization • Command Transmission • Test Mode • Blocking of Monitor Direction |
Supported Information | • Monitor direction:
* Status indications in monitor direction: from <16> to <30> * Supervision indications in monitor direction: <32>, <33>, from <35> to< 39>, <46>, <47> * Earth fault indications in monitor direction: from <48> to <52> * Fault indications in monitor direction: from <64> to <93> * Auto-reclosure indications in monitor direction: from <128> to <130> * Measurands in monitor direction: from <144> to <148> • Control direction: General commands in control direction: from <16> to <19>, from <23> to <26> |
IEC 60870-5-104 Server/ Client | |
General Specifications | • Server side supports serving up to 5 client
• Client side supports connecting up to 10 IEDs • Protocol implementation with configurable parameters conforms to the IEC 60870-5-104 specification edition 2 • Process Information in Monitor and Control Direction • CP56Time2a timestamp for Control Commands |
Supported Functions | • Station Initialization
• Interrogation • Read Procedure (Server side only) • Cyclic Data and Spontaneous Transmission (Server side only) • Clock Synchronization • Transmission of Integrated Totals • Direct and SBO command |
Supported Data Types | • Monitors Points:
Each supports maximum 1000 pts: Single Point, Double Point, Step Position, Bit String, Mea sured with Normalized Value, Measured with Scaled Value, Measured Short Floating Points Value, Integrated Totals. • Control Points: Each supports maximum 500 pts: Single Command, Double Command, Regulating Step Command, Set Point Command with Normalized Value, Set Point Command with Scaled Value, Set Point Command Short Floating Point, Bitstring. • Event Logging (Server Side only) Universal Event Buffer up to 20,000 Events |
Network Interface | |
Ethernet Port | 2 x RJ-45 |
LAN Mode | Dual Subnets or RSTP LAN Redundancy |
Compliance | IEEE 802.3 10BASE-T
IEEE 802.3u 100BASE-T(X) |
Serial Interface | |
Connector | RJ-45 |
Port | 8 or 16 |
Mode | RS-232/422/485, software selectable |
Baud Rate | 1,200~921,600 bps |
Parity | None, Odd, Even |
Data Bits | 5,6,7,8 |
Stop Bits | 1,2 |
Power Characteristics | |
Connector | IEC 60320-1 C14 AC Power Inlet (AC models) 5.08mm 3-pin Lockable Terminal Block (DC models) |
Input Voltage | 24-48 VDC for DC models 100-240 VAC for AC models |
Power Consumption | 0.54A @ 24 VDC
0.21A @ 100 VAC |
Power Redundancy | No |
Reverse Polarity Protection | Yes (DC Input only) |
Mechanicals | |
Housing | IP30 protection, metal housing |
Dimensions (W x H x D) | 436 mm x 43.5 mm x 200 mm |
Installation | 19” Rack Mount |
Reset Button | Yes |
Weight | 3.2kg (16 ports) / 3.0 kg ( 8 ports) |
Environmental Limits | |
Operating Temperature | -20°C ~ 70°C (-4°F ~ 158°F) |
Storage Temperature | -40°C ~ 85°C (-40°F ~ 185°F) |
Ambient Relative Humidity | 5 ~ 95% RH, (non-condensing) |
Software | |
Protocols | IPv4, ARP, ICMP, TCP, UDP, DHCP Client, DNS Client, Telnet, HTTP, HTTPS, SMTP/TLS,
SNMP v1/v2c/v3, Syslog, RSTP, OpenVPN or IPsec VPN (peer-to-peer or peer-to-side), with a maximum VPN throughput of 37.9Mbps(*), and PPTP |
* Testing conditions may affect the VPN throughput
Regulatory Approvals | ||||
Safety | EN 60950-1 | |||
EMC | FCC Part 15, Subpart B, Class A EN 55032, Class AEN 61000-3-2EN 61000-3-3EN 55024 |
|||
Test | Item | Value | Level | |
IEC 61000-4-2 | ESD | Contact Discharge Air Discharge |
±8KV
±15KV |
4
4 |
IEC 61000-4-3 | RS | Enclosure | 10 V/m | 3 |
IEC 61000-4-4 | EFT | AC Power Port DC Power Port Signal Port |
±4.0KV
±4.0KV ±2.0KV |
4
4 3 |
IEC 61000-4-5 | Surge | AC Power Port AC Power Port DC Power Port DC Power Port Signal Port |
Line-to Line±2.0KV Line-to Earth±4.0KV Line-to Line±1.0KV Line-to Earth±2.0KV Line-to Line±2.0KV |
4
4 3 3 4 |
IEC 61000-4-6 | CS | AC Power Port DC Power Port Signal Port |
10 Vrms
10 Vrms 10 Vrms |
3
3 3 |
IEC 61000-4-8 | PFMF | Enclosure | 1A/m | 3 |
IEC 61000-4-11 | DIP | AC Power Port | – | – |
Shock | IEC60068-2-27 | |||
Drop | ISTA Test Procedure 2A | |||
Vibration | IEC60068-2-64 | |||
RoHS | Yes | |||
MTBF
(MIL-HDBK-217F) |
XGP5908-SI-DC: 19.00 years; XGP5908-SI-US/EU: 19.03 years
XGP5916-SI-DC: 13.38 years; XGP5916-SI-US/EU: 13.38 years |
|||
Warranty | 5 years |