The TBL series is a new range of small DIN-rail mount power supplies which have been designed particularly with building- and factory automation applications in mind. The ultra-compact low profile cases fit in the standardized wall mounted control panels used in the building automation industry. The power supplies can be operated at full load across an ambient temperature range of –25°C to +60°C without need of additional cooling. Universal input voltage range and full compliance with all important safety and EMC standards qualifies the TBL series power supplies for worldwide markets. For commercial and residential applications requestingsafety class ll the models up to 90 Watt are approved to UL 1310

•  Low profile case, module depth only 55mm
• Fits into flat control panels used in building automation
• Safety class ll product
• UL 1310 class II, NEC class 2 compliance (models up to 90 W)
• UL 508 listed
• 5 power ranges from 15 to 150 W
• Universal input range 85 to 264 VAC
• Operating temperature range: –25°C to +70°C max.
• Adjustable output voltage
• Short circuit and overload protection
• DC–OK indicator
• Easy snap-on mounting on DIN-rail or with wall mounting bracket (included)
• 3-year product warranty

Product Details

Input Specifications


Input voltage  
– AC nominal rated 100 – 240 VAC; 50/60 Hz
• TBL 150 models: 100 – 120 / 220 – 240 VAC; 50/60 Hz
– AC range (designed for) 85 – 264 VAC; 47 – 63 Hz
• TBL 150 models: 85 – 132 / 187 – 264 VAC; 47 – 63 Hz
– DC range (designed for) 120 – 373 VDC (except TLB 150 models)
– Power derating at low input voltage 5% below 90 VAC or 127 VDC

Harmonic limits      
– EN 61000-3-2, Class Aa

Recommended circuit breaker 
– (characteristic C or slow blow fuse)    6.0 A

Output Specifications


Output voltage adjustable range
– 5 VDC model:  5.0 – 5.2 VDC  
– 12 VDC models: 12 – 16 VDC
– 24 VDC models: 24 – 28 VDC

Output regulation 1 %

Ripple and noise (20MHz bandwidth) <100 mV pk-pk

Electronic short circuit protection
– current limitation at 100 – 150 % typ.
(automatic recovery)

Overvoltage protection, trigger point
– 5 VDC model: 5.5 – 7.5 VDC
– 12 VDC models: 16 – 24 VDC
– TBL 030-124, TBL 150-124: 30 – 37 VDC
– TBL 015-124, TBL 060-124, TBL 090-124: 29 – 44 VDC

Hold-up time
– 115 VAC 230 VAC
– min. 10 ms min. 20 ms

General Specifications


Temperature ranges
– Operating –25°C to +70°C max.

Power derating  2.5 %/K above 60°C

Humidity (non condensing) 5 – 95 % rel. H

Temperature coefficient 0.02 %/K

Safety standards and certification
– UL 508 listed
– IEC 60950-1 2nd, EN 60950-1:2006+
– Am1:2010 +Am11:2009 +Am12:2011
– EN 50178, EN 60204-1, EN 61558-2-16
– CAN/CSA-C22.2 No. 60950-1-07
– UL 60950-1 2nd

Electromagnetic compatibility (EMC), emissions EN 61000-6-3
– Conducted RI suppression on input EN 55022 class B
– Radiated RI suppression EN 55022 class B

Electromagnetic compatibility (EMC), immunity EN 61000-6-2
– Electrostatic discharge (ESD) EN 61000-4-2 4 kV / 8 kV
– Radiated RF field immunity EN 61000-4-3 3 V/m
– Electrical fast transient / burst immunity EN 61000-4-4 1 kV / 0.5 kV
– Surge immunity line – ground EN 61000-4-5 2 kV
– Surge immunity line – line EN 61000-4-5 1 kV
– Surge immunity output EN 61000-4-5 0.5 kV
– Immunity to conducted RF disturbances EN 61000-4-6 3 V
– Mains voltage dips and interruptions EN 61000-4-11 30 % /10 mS, 60 % /100 mS

Environment
– Vibration acc. IEC 60068-2-6; 3 axis, sine sweep, 10 – 55 Hz, 0.075 mm
– Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 11 ms

Environmental compliance
– Reach www.tracopower.com/products/tbl-reach.pdf
– RoHS RoHS directive 2011/65/EU