Input power at no load 1.0 Watt max. Start-up voltage/under voltage shut down TCL 012 model: 8.4 VDC / 7.6 VDC TCL 024 & TCL 060 models: 17.2 VDC / 15.7 VDC Reverse polarity protection by internal fuse Efficiency 86 % typ. |
Output voltage adj. range 5 VDC model: 5.0 – 5.25 VDC 12 VDC models: 12.0 – 15.0 VDC 24 VDC models: 24.0 – 28.0 VDC Regulation – Input variation Vin min. to Vin max. 0.5 % max – Load variation 0…100% 0.5 % max Ripple and noise (20 MHz bandwidth) <50 mV pk-pk Electronic short circuit protection current limitation at 110 % typ. (constant current, automatic recovery) Overvoltage protection, trigger point 5 VDC model: <6.5 V 12 VDC models: <24 V 24 VDC models: <42 V |
Temperature ranges – Operating –25°C to +70°C max. – Storage (non operating) –25°C to +85°C Temperature derating 1.5 %/K above +50°C Humidity (non condensing) 95 % rel. H max. Temperature coefficient 0.02 %/K Switching frequency 55 – 180 kHz depending on load (frequency modulation) Isolation voltage (60 sec.) – Input/Output 1500 VDC Reliability, calculated MTBF at +25°C (according to IEC 61709) >2.5 Mio h Safety standards – Information technology equipment IEC 60950-1, EN 60950-1 (output SELV), UL Std. 60950-1 (2nd Edition) +Am1:2011, CAN/CSA-C22.2 No. 60950-1-07 +Am1:2011 – Industrial control equipment UL 508 – Electronic equipment for power installation EN 50178 – Electrical equipment for machines EN 60204 Safety approvals – CB test certificate (IEC 60950-1) www.tracopower.com/products/tcl-cb.pdf – UL approval www.ul.com -> certifications UL 508C listed, CSA C22.2 No.14 File e210002 – CSA certification UL 60950-1, CSA 60950-1-03 – GS certification Electromagnetic compatibility (EMC), emissions – Conducted RI suppression on input EN 55022 class ,B EN 61000-6-3 – Radiated RI suppression EN 55022 class B Electromagnetic compatibility (EMC), immunity – Electrostatic discharge (ESD) EN 61000-4-2 4 kV / 8 Kv, EN 61000-6-2 – Radiated RF field immunity EN 61000-4-3 10 V/m – Electrical fast transient / burst immunity EN 61000-4-4 Level 3 – Surge immunity EN 61000-4-5 Level 3 – Immunity to conducted RF disturbances EN 61000-4-6 10 Vrms Environmental compliance – RoHS RoHS directive 2011/65/EU |