TCL Series

Key Features:

The TCL series is a family of DIN-rail power supplies with an excellent price to performance ratio, Designed With tightly regulated output voltage and high immunity against electrical disturbances making them a reliable power source for sensitive loads in industrial process controls, machine tools and other equipment exposed to a difficult industrial environment.
•  For industrial, office and residential applications
•  Ultra compact plastic housing
•  Connection by spring clamp terminals or detachable screw terminal block
•  Reliable snap-on mounting on DIN-rails
•  Adaptor for wall mounting
•  Universal input 85–264 VAC, 50/60 Hz
•  Models with 5, 12, 24 & 48 VDC output
•  Output voltage adjustable
•  Power OK signal
•  Low ripple and noise
•  Overload and short-circuit protection
•  Parallel operation possible
•  Worldwide safety approvals
•  Redundancy module
•  3-year product warranty

Product Details

Input Specifications


Input voltage range
– 85–264 VAC/85–375 VDC
– TCL 240 model: 85–132/187–264 VAC autoselect (no DC input)
Output derating
– at operation between 85…93 VAC/85…130 VDC 15% for TCL 060 & TCL 120
20% for TCL 024-112 & TCL 024-124 & TCL 240
30% for TCL 024-105
Input frequency 47–63 Hz
Harmonic limits EN 61000-3-2, Class A
Input current at full load (typ.) (115 VAC / 230 VAC)
TCL 024 models: 0.35 A / 0.2 A
TCL 060 models: 1.2 A / 0.6 A
TCL 120 models: 2.0 A / 1.0 A
TCL 240 model: 3.3 A / 1.7 A
Recommended circuit breaker(characteristic C or slow blow fuse) 5.0 A

Output Specifications


Output voltage adjustable range

5.1 VDC model:  5.0 – 5.25 VDC

12 VDC models:  12 – 15 VDC (12 – 16 VDC for TCL 024-112)

24 VDC models:  24 – 28 VDC

48 VDC models:  48 – 56 VDC

Output regulation (10 to 90% load variation)    2.5 % (1 % for TCL 60-112)

Ripple and noise (20MHz bandwidth)    <50 mV pk-pk

Electronic short circuit protection

current limitation at 120 % typ. (constant current, automatic recovery TCL 24 models: foldback, automatic recovery)

Parallel operation    output current characteristic suitable for parallel operation of max. 5 units

(not for TCL 240-124)

Overvoltage protection, trigger point  

5.1 VDC model:  <6.5 VDC

12/24 VDC models:  <40 VDC

48 VDC models:  <60 VDC

Hold-up time (115 VAC / 230 VAC)

min. 15 ms / min. 125 ms

TCL 240 model:  min. 15 ms / min. 40 ms

Power OK signal(TCL 60 & TCL 120 only)    (trigger ,  output signal point  (reference to – Vout))

12 VDC models:  >11V  11.0 V ±1.0 V / 60 mA max.

24 VDC models:  >22V  22.0 V ±2.0 V / 30 mA max.

48 VDC models:  >44V  44.0 V ±4.0 V / 15 mA max.

Temperature ranges

– Operating    –10°C to +70°C max.

Temperature derating

– at 187…264 VAC or 265…375 VDC operation     1.7 %/K above 50°C

– at 93…132 VAC or 130…187 VDC operation  1.1 %/K above 40°C

– at 85…130 VDC operation    1.3 %/K above 30°C

Humidity (non-condensing)    95 % rel. H max.

Temperature coefficient    0.02 %/K

Switching frequency    55 – 180 kHz depending on load

Efficiency      88 % typ.

Safety standards

– Information technology equipment    IEC 60950-1, EN 60950-1 (output SELV),

– UL Std. 60950-1 (2nd Edition) +Am1:2011,

– CAN/CSA-C22.2 No. 60950-1-07 +Am1:2011

– Industrial control equipment    UL 508

– Electronic equipment for power installation EN 50178

– Electrical equipment for machines    EN 60204

– Safety transformers for SMPS    EN 61558-2-16

– Limited power source     NEC Class 2 (TCL 60 models only)

Safety approvals  – CB test certificate (IEC 60950-1)
– UL approval    UL 508C listed, CSA C22.2 No. 14

– UL approval    UL 60950, File e181381 (except TCL 240)

– CSA certification  UL 60950-1, CSA 60950-1-03

– BG certificate (by SIQ)    www.tracopower.com/products/tcl-bg.pdf

Environmental compliance

Reach

– RoHS    RoHS directive 2011/65/EU

Electromagnetic compatibility (EMC), emissions    EN 61000-6-3

Electromagnetic compatibility (EMC), immunity    EN 61000-6-2