Input voltage range – 85–264 VAC/85–375 VDC – TCL 240 model: 85–132/187–264 VAC autoselect (no DC input) Output derating – at operation between 85…93 VAC/85…130 VDC 15% for TCL 060 & TCL 120 20% for TCL 024-112 & TCL 024-124 & TCL 240 30% for TCL 024-105 Input frequency 47–63 Hz Harmonic limits EN 61000-3-2, Class A Input current at full load (typ.) (115 VAC / 230 VAC) TCL 024 models: 0.35 A / 0.2 A TCL 060 models: 1.2 A / 0.6 A TCL 120 models: 2.0 A / 1.0 A TCL 240 model: 3.3 A / 1.7 A Recommended circuit breaker(characteristic C or slow blow fuse) 5.0 A |
Output voltage adjustable range 5.1 VDC model: 5.0 – 5.25 VDC 12 VDC models: 12 – 15 VDC (12 – 16 VDC for TCL 024-112) 24 VDC models: 24 – 28 VDC 48 VDC models: 48 – 56 VDC Output regulation (10 to 90% load variation) 2.5 % (1 % for TCL 60-112) Ripple and noise (20MHz bandwidth) <50 mV pk-pk Electronic short circuit protection current limitation at 120 % typ. (constant current, automatic recovery TCL 24 models: foldback, automatic recovery) Parallel operation output current characteristic suitable for parallel operation of max. 5 units (not for TCL 240-124) Overvoltage protection, trigger point 5.1 VDC model: <6.5 VDC 12/24 VDC models: <40 VDC 48 VDC models: <60 VDC Hold-up time (115 VAC / 230 VAC) min. 15 ms / min. 125 ms TCL 240 model: min. 15 ms / min. 40 ms Power OK signal(TCL 60 & TCL 120 only) (trigger , output signal point (reference to – Vout)) 12 VDC models: >11V 11.0 V ±1.0 V / 60 mA max. 24 VDC models: >22V 22.0 V ±2.0 V / 30 mA max. 48 VDC models: >44V 44.0 V ±4.0 V / 15 mA max. Temperature ranges – Operating –10°C to +70°C max. Temperature derating – at 187…264 VAC or 265…375 VDC operation 1.7 %/K above 50°C – at 93…132 VAC or 130…187 VDC operation 1.1 %/K above 40°C – at 85…130 VDC operation 1.3 %/K above 30°C Humidity (non-condensing) 95 % rel. H max. Temperature coefficient 0.02 %/K Switching frequency 55 – 180 kHz depending on load Efficiency 88 % typ. Safety standards – Information technology equipment IEC 60950-1, EN 60950-1 (output SELV), – UL Std. 60950-1 (2nd Edition) +Am1:2011, – CAN/CSA-C22.2 No. 60950-1-07 +Am1:2011 – Industrial control equipment UL 508 – Electronic equipment for power installation EN 50178 – Electrical equipment for machines EN 60204 – Safety transformers for SMPS EN 61558-2-16 – Limited power source NEC Class 2 (TCL 60 models only) Safety approvals – CB test certificate (IEC 60950-1) – UL approval UL 60950, File e181381 (except TCL 240) – CSA certification UL 60950-1, CSA 60950-1-03 – BG certificate (by SIQ) www.tracopower.com/products/tcl-bg.pdf Environmental compliance – Reach – RoHS RoHS directive 2011/65/EU Electromagnetic compatibility (EMC), emissions EN 61000-6-3 Electromagnetic compatibility (EMC), immunity EN 61000-6-2 |