TFP Series

Key Features:

The TFP series is designed to operate in shallow electric control cabinets with low profile depth and DIN rail or wall mounting, And with a unique thermo-mechanical construction combining optimized heat transfer of power components and high mechanical ruggedness

•  Robust and compact low profile metal case for mounting in flat racks
•  Low heat dissipation and a high efficiency of 92% typical
•  Worlwide Safety approval package.
•  ATEX certification and IECEx test repor (opt. EX)
•  Wide AC and DC input voltagee range 85 – 264 VAC and 90 – 280 VDC
•  Industrial operating temperature range: –25°C to +70°C
•  Active isolation diode
•  Mains current with power factor >98%
•  Adjustable output voltage
•  Protection agains short-circuit, overvoltage and over-temperature
•  Power OK signal, Remote On/Off
•  Extended functional features (opt.)
•  Wall mounting (opt.)
•  3-year product warranty

Product Details

Input Specifications


Input voltage range

AC input:  85 – 264 VAC universal input

DC input:  90 – 280 VDC (external fuse or circuit breaker required)

Input voltage frequency    45 – 65 Hz

Harmonic limits     EN 61000-3-2, Class A (for limited output power)

Holdup time

85 VAC   20 ms typ.

184 VAC  20 ms typ.

Inrush current

115 VAC  < 15 A

230 VAC  < 30 A

Standby Power   (external ON/OFF activated)

250 W model:  3W

500 W model:  5W

750 W model:  7W

Start-up delay      250 ms typ.

Efficiency (at nominal load)

115 VAC  91.5 % typ.

230 VAC  93 % typ.

Output Specifications


Output voltage adj. range

– 24 VDC models:  24 – 28,8 VDC (SELV voltage)

– 48 VDC models:  48 – 60 VDC

– 72 VDC models:  60 – 74 VDC

Regulation

– Input variation    0.5 % max.

– Load variation (10–90 %)    1.0 % max.

Ripple and Noise (20MHz bandwidth)

< 100 mV pk-pk

Electronic short circuit protection

current limitation at Imax.

constant current, automatic recovery

Output overvoltage protection

– 24 VDC models:  < 35 V

– 48 VDC models:  < 70 V

– 72 VDC models:  < 100 V

Overload protection    electronic overload protection

Over temperature protection   

switch off at overtemperature, automatic restart

Power back immunity

– 24 VDC models:  30 V

Status indicator

dual color LED (green: DC ok, red: DC off)

Power OK signal

– trigger threshold:  – 24 VDC models:  21.5 – 22.5 V

– 48 VDC models:  TBD

– 72 VDC models:  TBD

– active output signal:  – 12 VDC models:  11.0 V ±1.0 V

(reference to –Vout) TBD  (20 mA max. for TSP 070, 40 mA max. for TSP 140)

– 24 VDC models:  22.0 V ±2.0V / 20 mA max.

– relay output    DC OK = contact closed

– rated: 30 VDC/1.0 A for 24 VDC models

– rated: TBDfor 48 VDC model

– rated: TBDfor 72 VDC models

Max. capacitive load
– unlimited

Temperature range

– Operating    –25°C to +70°C max.

(optional –40ºC to +70ºC)

– Storage    –25°C to +85°C

Power derating      3 %/K above 60ºC

Humidity (non-condensing)    95 % rel. H max.

Temperature coefficient    0.02 %/K

Isolation       according to IEC/EN 60950-1, UL 60950-1, UL 508

Safety standards

– Information technology equipment  IEC/EN 60950-1, UL 60950-1, CSA-C22.2 No. 60950-1-03

– Industrial control equipment    UL 508, CSA-C22.2 No. 107

– Electrical equipment for machines EN 60204

– Electronic equipment for power installation EN 50178

– Safety transformers for SMPS    EN 61558-2-4, EN 61558-2-4

– Control equipment for hazardous location UL 60079-15

(Class I, Division 2, Groups A,B,C,D AEx n C II C T4 U)

IEC/EN60 079-15(Class I, Zone 2, EEx nC II C T4 U),

( II3G EEX nAC IIC T4 (T3 with limited power)

Safety approvals and  certifications

– CB report   for IEC/EN 60950-1

– UL approvals    UL 60950-1 rec. File: e181381, UL 508C listed File: e210002

– CSA certification   (file no. 219759) for UL 60950-1, UL 508, UL 60079-15-02,

ANSI/ISA 12.12.01, CSA-22.2 No. 60950-1-03,

CSA C22.2 No. 107, CSA 60079-15-02

–  II3G ATEX 94/9/EC     certificate no. EPS 12 ATEX 1 424 X (option -EX only)

– IECEx test report    for IEC 60079-15

– BG certification     EN 60950-1, EN 60204-1, EN 61558-2-16, EN 50178

Electromagnetic compatibility (EMC), Emissions    EN 61000-6-3, EN 61204-3

– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,

– Radiated RI suppression    EN 55011 class B, EN 55022 class B,

Electromagnetic compatibility (EMC), Immunity    EN 61000-6-2, EN 61204-3

– Electrostatic discharge (ESD)    IEC / EN 61000-4-2  4 kV / 8 kV  criteria A

– Radiated RF field immunity    IEC / EN 61000-4-3  10 V / m  criteria A

– Electrical fast transient / burst immunity IEC / EN 61000-4-4  2 kV  criteria B

– Surge immunity    IEC / EN 61000-4-5  1 kV / 2 kV  criteria B

– Immunity to conducted RF disturbances IEC / EN 61000-4-6  10 V  criteria A

– Power frequency field immunity    IEC / EN 61000-4-8  30 A / m  criteria A

– Mains voltage dips and interruptions IEC / EN 61000-4-11  criteria B/C

– Voltage sag immunity    SEMI F47

Environment  


– Vibration acc. IEC 60068-2-6;     3 axis, sine sweep, 10 – 55 Hz, 2 g, 11 oct/min

– Shock acc. IEC 60068-2-27    3 axis, 25 g half sine, 11 ms