TPC Series

Key Features:

The TPC series is a family of lightweight DIN-rail power supplies with an excellent price to performance ratio. Designed for class I operation in industrial and residential environments with an optional active current sharing redundancy module.
•  For industrial, office and residential environments
•  Meets European ErP directive (green mode), <0.3 W no load power consumption
•  High efficiency across full load range
•  Compact plastic casing
•  Reliable snap-on mounting on DIN-rails or with wall mounting bracket (not included)
•  Universal input 85–264 VAC, 47–63 Hz
•  Models with 5, 12, 24 & 48 VDC output
•  Output voltage adjustable
•  Power good signal
•  Low ripple and noise
•  Overload and short-circuit protection
•  Optional module for parallel and redundant operation
•  Worldwide safety approval package
•  3-year product warranty

Product Details

Input Specifications


Input voltage range

– AC nominal rated     110 – 240 VAC, 50-60 Hz

– AC range(designed for)    85 – 264 VAC, 47-63 Hz

– DC nominal rated    130 – 300 VDC

– DC range (designed for)    90 – 375 VDC

Output derating

– at operation <100 VAC  -2.5% /V

– at operation <130 VDC  -1.0 % /VDC

Standby power consumption

– TPC 030 and 055 models:  < 0.3 W

– TPC 080 and 120 models:  < 0.5 W

Harmonic limits      EN 61000-3-2, Class A

Recommended circuit breaker, characteristic C    6.0 – 16.0 A

Output Specifications


Output voltage adjustable range 

– 5 VDC model:  5.0 – 6.0 VDC

– 12 VDC models:  12 – 15 VDC

– 24 VDC models:  24 – 28.8 VDC

– 48 VDC models:  48 – 56 VDC

Regulation

– Input variation    0.5 % max.

– Load variation (0–100 %)  5 VDC models:  0.75 % max. other models:  0.5 % max.

Ripple and noise (20MHz bandwidth)    100 mVpk-pk max.

Short circuit protection    <200 % of Iout nom.

Overvoltage protection(% of max. adjustable voltage) 

– 5 VDC model:  <180 %

– 12 VDC models:  <170 %

– 24 VDC models:  <160 %

– 48 VDC models:  <107 %

Power back immunity

– 125 % of nominal Vout

Start-up time      2 sec. max.

Hold-up time (115 VAC / 230 VAC)    min. 15 ms / min. 40 ms

Power OK signal

– trigger     80 – 95 %

– PNP open collector max. current  48 VDC models:  5 mA

other models:  10 mA

Temperature ranges

– Operating    –25°C to +70°C max.

Temperature derating    2.5 %/K above 50°C

Humidity (non-condensing)    95 % rel. H max.

Temperature coefficient    0.02 %/K

Remote On/Off       10 mA curent source

– application document  www.tracopower.com/overview/tpc

Efficiency (average at power consumption 25-100%)

– TPC 030-105:  79 %

– other 30 Watt models:  84 %

– other models:  87 %

Safety approvals

– CB test certificate    IEC 60950-1:2005 2nd Ed, Am 1:2009

– SIQ type approved    EN 60950-1 :2006 + Am 1 :2010 +  Am 11 :2009 + Am 12:2011

– CSA certificate of compliance    UL 60950-1-2nd Ed

– CSA 60950-1-07-2nd Ed

– UL certificate of compliance    UL 508, CSA C22.2 No.107.1-01

– SIQ type approved    EN 60204-1:2006 + A1:2009,

– EN 61558-2-8:2010, EN 61558-2-16:2009,

– EN 50178:1997

Environmental compliance

– Reach declaration document    www.tracopower.com/overview/tpc

– RoHS    RoHS directive 2011/65/EU

EMC 

emissions    IEC 61000-6-3 (residential environment)

immunity    IEC 61000-6-2 (industrial environment)

SEMI F47