Programming | |
Programming Editor | Telediagram Software |
Programming Language | Function Block Diagram(FBD), Ladder |
Input / Output | |
Digital Input | 16 Channel, Optical Isolation |
Digital Output | 8 Channel, 2A@30VDC, PNP Transistor, Optical Isolation |
Analog Input | 4 Channel, 4-20mA, 0-20mA, Accuracy 1% |
Analog Output | 2 Channel, 4-20mA, 0-20mA, Accuracy 1% |
Relay Output | 4 Channel, 3A@30VDC – 5A@250VAC, NO Contact |
Expansion Capability | |
Total I/O | Up to 1024 Points |
Integrated Communication Ports | |
Integrated GSM/GPRS | Quad-Band 850 / 900 / 1800 / 1900 / 2100 MHz |
Integrated UMTS/HSPA Modem | Max. 14.4 Mbps(DL) / Max. 5.76 Mbps(UL) |
Ethernet | 1 Port, 10/100 Mbps |
RS485 | 1 Port, 3 kV ESD Protection, Galvanic and Optical Isolation |
RS232 | 1 Port |
USB | 1 Port, USB Type B |
Communication Protocols | |
Master Communication Protocols | MODBUS, IEC62056-21 |
Slave Communication Protocols | MODBUS, IEC60870-5-101, IEC60870-5-104 |
Mikrodev Specific | DEVNET (UDP Based Data Exchange Protocol) |
IoT Protocol | MQTT |
IP protocols | TCP, UDP, NTP, SNTP, HTTP, TFTP, DHCP, DNS |
Maximum Connection Count | |
Number of Server Socket | 16 |
Number of Client Socket | 32 |
Number of Client Sockets per TCP Server Socket | 16 |
Data Logger Functionality | |
SD Card Support | Micro SD Card |
Programmable Data Logging Trigger Functions | Yes |
Retentivity | |
Protecting the Last Values of Process Data in case of Power Cut | Yes |
Retentive Memory Capacity | 128 Block/Register Type |
Event Log | |
Event Log with Time Tag | Yes |
Event Log Time Resolution | 1 ms |
Maximum Event Log | 20000 |
Real Time Clock and Calendar | |
Real-time Clock | Integrated |
NTP Client Support | Yes |
Time Synchronization via MODBUS | Yes |
Battery Status/Level Reading Functions | Yes |
RTC Battery | CR2032 Lithium, Battery Life: 3 Years |
Special GSM Functions | |
Receiving and Parsing SMS Messages | Yes |
SMS Composition and Sending Functions | Yes |
Accepting DTMF Calls and Code Parsing Functions | Yes |
DTMF Call Generation and Code Sending Functions | Yes |
LED Signals | |
Power | 1 LED Green |
Running Status | 1 LED Green |
Connection | 1 LED Green |
Warning/Error | 1 LED Red |
Digital Inputs | 16 LED Blue |
Digital Output | 8 LED Blue |
Relay Output | 4 LED Blue |
Environmental Conditions | |
Operating Temperature | -25 / +75 C |
Storing Temperature | -30 / +80 C |
Humidity | 5..95 RH |
Protection Standard | IP20 |
Operating Altitude | 0..2000 m |
Electrical Wiring | |
Inputs and Outputs | Demountable Terminal Block with Screw, (pitch 5.08 mm) |
Power Supply Input | Demountable Terminal Block with Screw, (pitch 5.08 mm) |
Standards | |
IEC 60255-5 | 2.5 kV Isolation |
IEC 61000-4-2 | 6 kV Direct, 8 kV Air Discharge |
IEC 61000-4-6 | RF Field Influence 10 Vrms (150 kHz – 80 MHz) |
IEC 61000-4-18 | 2.5 kV (400/s Repetition with 1 MHz Electronic Wave) |
Supply | |
Supply Voltage | 12..36 VDC |
Supply Current | 100 mA @ 24 VDC |
Warranty | |
Duration | 24 Months |
Certificates | CE |