| IEC61850 Server/ Client | |
| Supported Functions | · Generic access to the data (Read, Write)
· 8 Logical Devices per Port · GOOSE (Generic Object Oriented Substation Event) · (*)Being other protocols not Real-Time, there is no guarantee that GOOSE message is generated within 1 ms from the event itelf. |
| Supported Control Type of commands | · Direct-with-Normal-Security Select Before Operate (SBO)-with-Normal-Security
· Direct-with-Enhanced Security Select Before Operate (SBO)-with-Enhanced-Security |
| Implemented Protocol Subsets | · IEC 61850-6 (Substation Configuration Language Description: SCL)
· IEC 61850-7-1 (Principles and Models) · IEC 61850-7-2 (Abstract Communication Service · Interface: ACSI · IEC 61850-7-3 (Common Data Classes: CDC) · IEC 61850-7-4 (Logical Nodes and data Object Classes) · IEC 61850-8-1 (Mapping to Manufacturing Message Specification: MMS) · Edition 1 & Edition 2 are both Supported |
| DNP3 Server/ Client/ Master/ Slave | |
| General Specifications | · Serial Mode or Ethernet with TCP or UDP Mode
· Server side supports serving up to 5 client in TCP Mode · Client side in a single RS-485 port, supports connecting up to 16 IEDs · Client side supports connecting up to 16 IEDs · Maximum Fragment size 2048 octets · Protocol implementation with configurable parameters conforms to IEEE Std 1815-2012 level 2 |
| Supported Functions | · Time Synchronization generic access to the data (Read, Write)
· Commands with or without preselection (Select, Operate, Direct Operate) · Transmission of time-tagged events · Self-address |
| Supported DNP3 Object Library | · Binary Inputs up to 8000 pts
· Binary Outputs up to 2000 pts · Double Inputs up to 4000 pts · Analog Inputs up to 250 pts · Analog Outputs up to 250 pts · Counters up to 250 pts |
| IEC 60870-5-103 Master/ Slave | |
| General Specifications | · Protocol implementation with configurable parameters conforms to the IEC 60870-5-103:1997
· Master supports connecting up to 16 IEDs · Process Information in Monitor and Control Direction · Unbalanced Modes |
| Supported Functions | · Station Initialization, Supports reset FCB and CU
· General Interrogation · Clock Synchronization · Command Transmission · Test Mode · Blocking of Monitor Direction |
| Supported DNP3 Object Library | · Monitor direction:
– Status indications in monitor direction: from <16> to <30> – Supervision indications in monitor direction: <32>, <33>, from <35> to < 39>, <46>, <47> – Earth fault indications in monitor direction: from <48> to <52> – Fault indications in monitor direction: from <64> to <93> – Auto-reclosure indications in monitor direction: from <128> to <130> – Measurands in monitor direction: from <144> to <148> · Control direction: |
| DNP3 Server/ Client/ Master/ Slave | |
| General Specifications | · Server side supports serving up to 5 client
· Client side supports connecting up to 10 IEDs · Protocol implementation with configurable parameters conforms to the IEC 60870-5-104 specification edition 2 · Process Information in Monitor and Control Direction · CP56Time2a timestamp for Control Commands |
| Supported Functions | · Station Initialization
· Interrogation · Read Procedure (Server side only) · Cyclic Data and Spontaneous Transmission (Server side only) · Clock Synchronization · Transmission of Integrated Totals · Direct and SBO command |
| Supported DNP3 Object Library | · Monitors Points: Each supports maximum 1000 pts: Single Point, Double Point, Step Position, Bit String, Measured with Normalized Value, Measured with Scaled Value, Measured Short Floating Points Value, Integrated Totals.
· Control Points: Each supports maximum 500 pts: Single Command, Double Command, Regulating Step Command, Set Point Command with Normalized Value, Set Point Command with Scaled Value, Set Point Command Short Floating Point, Bitstring. · Event Logging (Server Side only) Universal Event Buffer up to 20,000 Events |
| Network Interface | ||
| Ethernet Port | 2x 10/100BASE-T(X) RJ-45 or 2x 100/1000 SFP Slots | |
| LAN Mode | Dual Subnets or LAN Redundancy | |
| Compliance | IEEE 802.3 for 10BASE-T IEEE 802.3u for 100BASE-T(X) IEEE 802.3af for Power over Ethernet PD (PoE version only) IEEE 802.3u for 100BASE-X (SFP version only) IEEE 802.3z for 1000BASE-X (SFP version only) |
|
| Serial Interface | ||
| Connector | 1×2 5 pin 3.81mm Terminal Block, or D-sub9 connector | |
| Port | 4 | |
| Mode | RS-232/422/485, software selectable | |
| Baud Rate | 1,200~921,600 bps | |
| Parity | None, Odd, Even | |
| Data Bits | 7,8 | |
| Stop Bits | 1,2 | |
| Isolation | 3 KV | |
| USB Interface | ||
| Speed | USB 2.0 | |
| Connector | USB A Type *1 | |
| Power Characteristics | ||
| Connector | Terminal Block | |
| Input Voltage | 12-48 VDC, or 48 VDC (supplied by PoE) | |
| Power Consumption | 0.65A @12 VDC (max.) | |
| Power Redundancy | Yes | |
| Reverse Polarity Protection | Yes | |
| Relay Output | 1A@30 VDC (normal open) | |
| Mechanicals | ||
| Dimensions (W x H x D) | 55mm x 145mm x 113mm | |
| Installation | DIN-Rail or Wall-Mount (optional kit) | |
| Reset Button | Yes | |
| Weight | 1000g | |
| Environmental Limits | ||
| Operating Temperature | -40°C ~ 85°C (-40°F ~ 185°F) | |
| Storage Temperature | -40°C ~ 85°C (-40°F ~ 185°F) | |
| Ambient Relative Humidity | 5 ~ 95% RH, (non-condensing) | |
| Software | ||
| Protocols | IPv4, ARP, ICMP, TCP, UDP, DHCP Client, DNS Client, Telnet, HTTP, HTTPS, SMTP/TLS, SNMP v1/v2c/v3, Syslog, 802.1D-2004 RSTP, IPsec VPN peer-to-peer and peer-to-side, OpenVPN client/server (maximum VPN throughput of 37.9Mbps*), and PPTP | |
| Configuration | Web interface, Telnet, Device Management Utility (basic device settings) eNode Designer windows Utility (protocol conversion related settings) |
|
| Regulatory Approvals | ||||
| Safety | IEC/EN 61010-1, IEC/EN61010-2-201, UL61010-1, UL61010-2-201 | |||
| EMC | FCC Part 15, Subpart B, Class A
EN 55032, EN 61000-3-2, EN 61000-3-3, EN 55024, EN 61000-6-2, EN 61000-6-4 |
|||
| Test | Item | Value | Level | |
| IEC 61000-4-2 | ESD | Contact Discharge Air Discharge |
±6KV
±8KV |
3
3 |
| IEC 61000-4-3 | RD | 80-1000MHz
1.4-2.0GHz 2.0-2.7GHz |
10 V/m
3 V/m 1 V/m |
3
2 1 |
| IEC 61000-4-4 | EFT | AC Power Port DC Power Port Signal Port |
±2.0KV
±2.0KV ±1.0KV |
3
3 3 |
| IEC 61000-4-5 | Surge | AC Power Port AC Power Port DC Power Port DC Power Port Signal Port |
Line-to Line±2.0KV Line-to Earth±2.0KV Line-to Line±1.0KV Line-to Earth±1.0KV Line-to Earth±2.0K |
4
3 3 2 3 |
| IEC 61000-4-6 | CS | 0.15-80MHz | 10 Vrms | 3 |
| IEC 61000-4-8 | PFMF | 0.15-80MHz | 30 A/m | 4 |
| IEC 61000-4-11 | DIP | AC Power Port | – | – |
| Shock | IEC 60068-2-27 | |||
| Drop | IEC 60068-2-32 | |||
| Vibration | IEC 60068-2-64 | |||
| RoHS | Yes | |||
| REACH | 14.56 Years (according to MIL-HDBK-217F) | |||
| MTBF | 5 years | |||
| Warranty | IEC 60068-2-27 | |||