| Model Name | XSP5908 (8 ports); XSP5916 (16-ports) |
| Network interface | |
| Speed | IEEE 802.3 10BaseT IEEE 802.3u 100BaseT(X) – RJ45 version IEEE 802.3u 100Base-FX – SFP version |
| Connector ports | RJ45 x 6 (RJ45 version) SFP x 6 (SFP version) |
| Serial Interface | |
| Connector | D-Sub9 (DB models, supporting only 5-pin RS-232 mode) or 5.08mm 5-Pin Terminal block (TB Models) |
| Ports | 8 (XSP5908) or 16 (XSP5916) |
| Mode | RS-232/422/485 Software selectable |
| Serial port isolation | 3 kV isolation (SiS version only) |
| Baud Rate | 1,200 ~ 921,600 bps software selectable |
| Parity | None, Odd, Even, Mark, Space |
| Data Bits | 5, 6, 7, 8 software selectable |
| Stop Bits | 1, 2 software selectable |
| Flow Control | None, Xon/Xoff, RTS/CTS (RS-232 only) |
| Power | |
| Input Voltage | Redundant 24-48 VDC or
Redundant 100-240 VAC/ 100-370 VDC (HV Series) |
| Input Current | 0.73 A @ 24 VDC
0.35 A @ 100 VAC 0.20 A @ 100 VDC |
| Power Consumption | Approximately 20 W |
| Power Redundancy | Yes |
| Connector | 10-Pin Terminal Block |
| Reverse Polarity Protection | Yes |
| Physical Characteristics | |
| Housing Dimension (W x H x D) Weight Installation Reset Button |
IP30 SPCC housing 440.6 x 44 x 309 mm (1U Rack-mount) 4 kg 19” Rack mount (Rack-mount kit included) Yes |
| Environmental Limits | |
| Operating Temperature Storage Temperature Ambient Relative Humidity |
-40°C~85°C (-40°F~185°F) -40°C~85°C (-40°F~185°F) 5%~95%, 55°C (Non-condensing) |
| Software | |
| Protocols | IPv4, ICMP, TCP, UDP, DHCP Client, SNMPv1,v2c,v3, HTTP, HTTPS, Telnet, RFC2217, 802.1D-2004 RSTP, Security through OpenVPN Client/Server or IPsec VPN (peer-to-peer or peer-to-side) with up to 37.9Mbps VPN throughput, PPTP, and SMTP/TLS |
| Configuration | AGATEL Management Utility, Web UI, Telnet, Console |
| VirtualCOM | Windows/Linux redirection software |
| Modbus Features | |
| Supported Modes | Ethernet: Modbus TCP Server/Client(or VCOM); Serial: Modbus RTU/ASCII (master/slave) |
| Maximum number of clients/slaves | Modbus TCP: Maximum 16 clients; Maximum 247 slaves |
| Regulatory Approvals | ||||
| Safety | EN 61010-2-201 | |||
| EMC | FCC Part 15, Subpart B, Class B, EN 55032, Class B, EN 61000-6-2 Class B, EN 61000-3-2, EN 61000-3-3, EN 55024, EN 61000-6-4, IEC 61850-3 / IEEE 1613 |
|||
| Test | Item | Value | Level | |
| IEC 61000-4-2 | ESD | Contact Discharge Air Discharge |
±8kV
±15kV |
4
4 |
| IEC 61000-4-3 | RS | Radiated (enclosure) | 10 V/m | 3 |
| IEC 61000-4-4 |
EFT |
AC Power Port DC Power Port Signal Port |
±4.0KV
±4.0KV ±4.0KV |
4
4 4 |
| IEC 61000-4-5 | Surge | AC Power Port AC Power Port DC Power Port DC Power Port Signal Port |
Line-to Line±2.0KV Line-to Earth±4.0KV Line-to Line±1.0KV Line-to Earth±2.0KV Line-to Earth±2.0KV |
4
4 3 3 4 |
| IEC 61000-4-6 |
CS |
AC Power Port DC Power Port Signal Port |
10 V rms | 3 |
| IEC 61000-4-8 | PFMF | Enclosure | 100 A/m | 5 |
| IEC 61000-4-10 | Damped Oscillato- ry Magnetic Field | Enclosure | 100 A/m | 5 |
| IEC 61000-4-11 | DIP | AC Power Port | – | – |
| IEC 61000-4-12 | Damped Oscillatory |
AC Power Port Signal Port |
2.5 KV common, 1 KV differential
2.5 KV common, 1 KV differential |
3
3 |
| Shock | MIL-STD-810F Method 516.5 | |||
| Drop (Freefall) | MIL-STD-810F Method 516.5 | |||
| Vibration | MIL-STD-810F Method 514.5 C1 & C2 | |||
| RoHS | Yes | |||
| MTBF | XSP5916-6S-SI-HV: 9.18 years; XSP5916-6S-SI: 8.63 years | |||
| Warranty | 5 Years | |||